- Description
- Reviews (0)
Description
Capacity: 10000VA / 10000W (10kVA / 10kW)
Topology: Online double-conversion
Waveform: Sine wave
Outlets: Terminal
Features:
• Sine wave output
• DSP technology
• 1.0 power factor
• <2% output voltage regulation
• Low THDi & THDv
• Step-down isolation transformer for 100 / 110 / 115 / 120V and 208 / 220 / 230 / 240Vac output voltage
• ECO Mode
• Intelligent slot for an optional network card
• Optional external battery bank
• Parallel up to 3 units
OVERVIEW | |
Model | TAC-TW10KD |
Capacity | 10000VA / 10000W |
Topology | Online double-conversion |
INPUT | |
Voltage | 208 / 220 / 230 / 240Vac |
Voltage Range | 176 – 276Vac at full load / 110 – 176Vac derating at 50% load linearly |
Frequency | 45 – 55Hz / <60% rated load: 40 – 70Hz >60% rated load: 54 – 66Hz |
Power Factor | >0.99 at 100% load |
THDi | <3% at linear load / <5% at non-linear load |
Inlet | Hardwire terminal |
OUTPUT | |
Output Voltage | 208 / 220 / 230 / 240Vac & 100 / 110 / 115 / 120Vac (selectable) |
Frequency Range (on Battery) | 50 / 60 Hz +/- 1% |
Voltage Regulation | <1% |
THDv for Linear-Load | <2% at linear load |
Crest Factor | 3:1 |
Wave Form (on Battery) | Sine wave |
Outlet | 1 x hardwire terminal |
Parallelled Units | Up to 3 x TAC-TW10KD (N+2) |
TRANSFER TIME | |
Line To/From Battery | 0ms |
Inverter To/From Bypass | 0ms |
EFFICIENCY | |
Line Mode | 90% at full load with batteries fully charged |
ECO Mode | 93% at full load with batteries fully charged |
BATTERY | |
Chemistry | Sealed lead-acid |
Quantity & Size | 16 x 12V / 7Ah (option to expand to 20 pieces) |
Recharge Time | 3 hours to 90% capacity (internal batteries only) |
Charging Current | 1.4A |
Rated Battery Voltage | 192Vdc (240Vdc at 20 x 12V / 7Ah) |
PROTECTION | |
Emergency Power Off (EPO) | Yes |
Overload Protection | Yes |
Overcharge Protection | Yes |
Network / Phone / Fax Surge Suppression | Yes, RJ-11/45 combo ports (1-in, 1-out) |
Surge Suppression | Yes |
EMI / RFI Filter | Yes, full time |
ADDITIONAL FEATURES | |
EPO Tab | Yes, emergency power off tab |
MBS | Yes, maintenance bypass switch to safely route electricity during maintenance and servicing |
Load Segment Control | Yes |
ECO Mode | Yes |
External Battery Connector | No, must purchase TAC-TW10KLD (extended runtime model) for this feature |
Parallel Units | Yes, up to 3 additional for N+2 or N configuration |
COMMUNICATION | |
USB Port | Yes, for power management software to control and monitor the UPS conditions |
RS232 Port | Yes, for power management software to control and monitor the UPS conditions |
Software | Compatible with Windows 10/8/7/ Server 2012 R2 / 2008 R2 / Linux 32-Bit / 64-Bit / Sun Solaris / IBM Aix / Compaq True64 / SGIIRIX / FreeBSD / HP-UX / mac |
Intelligent Slot | Yes for SNMP, AS400, or relay card |
STATUS INDICATORS | |
LCD Screen | Yes, for Input/Output Voltages, Battery Level, Fault, status codes, and more |
Audible Alert | Yes |
WARRANTY | |
Warranty | 2-Year: Equipment and $25,000 Connected Equipment Warranties. 2-Year: Battery Warranty. See Terms of Use and Warranty pages for additional information. |
PHYSICAL | |
Color | Black |
Form Factor | Tower |
Product Dimensions (DWH) | 24.9 x 11.8 x 31.7 in / 633.2 x 300 x 805.5 mm |
Product Weight | 269.6 lb / 122.2 kg |
Product specifications are subject to change without further notice. Maruson assumes no responsibility, and disclaims all liability, for any damages that may result from the use of this information or for any errors or omissions. Battery backup time varies with equipment, configuration, battery age, temperature, etc. |